| Technical Data |
|
|
| Temperature range |
: |
Flexing -5ºC to + 80ºC |
| |
|
Fixed installation -40ºC to + 80ºC |
| Nominal voltage |
: |
0,14 mm2 = 350 V > 0,25 mm2 = 500 V |
| Test Voltage |
: |
Up to 0,25 mm2 1200 V from 0,34 mm2 2000 V |
| Breakdown Voltage |
: |
Up to 0,25 mm2 2400 V from 0,34 mm2 4000 V |
| Insulation resistance |
: |
Min. 20MOhm x km |
| Capacitance |
: |
(approx value) at 800 HZ 0,14mm2 120 > 0,25 mm2 150 pF/m |
| Inductance |
: |
approx 0,65 mH/km |
| Impedence |
: |
approx 78 Ohm |
| Minimum bending radius |
: |
Flexing : 7,5 x cable |
| |
|
Fixed installation : 4 x cable |
| Radiation resistance |
: |
up to 80 x 1.000.000 cJ/kg (up to 80 Mrad) |
| Cable Construction |
: |
- Bare copper, conductors, stranded to IEC 60228 cl 5 |
| |
|
- Special PVC core insulation T12 |
| |
|
- Colour coded to DIN 47100, but without colour repetition |
| |
|
- Special PVC outer sheath TM2, to DIN VDE 0281 part 1 |
| |
|
- Colour grey |
| |
|
- Extremely oil resistant |
| |
|
- PVC self-extinguishing and flame retardant according to IEC 60332-1 |
| Application |
: |
For flexible use with free movements without tensile stress or forced movements in dry, |
| |
|
moist and wet zones, but not suitable in the open, wherever the construction requires a |
| |
|
minimum outer diameter. Especially for such areas as tool making and machine industries |
| |
|
as well as in electronic, computer, measurement and control sectors. |