LiYY  
LiY-CY  
LiYY-Twisted Pair  
LiYCY-Twisted Pair  
Li2YCY-PiMF  
YSLYCY-JZ  
YSLYCY-JB  
LiYCY-OZ  
LiYCY-JZ  
Li2YCY  
Li2YCY PE-insulated, Low capacitance
250 V
Cable Construction : - Bare copper stranded wire, 7-wires, adapted to DIN VDE 0881, Suitable for Termi-Point
    and solder-free connection technique
    - Conductor make-up
    0,22 mm2 = 7 x 0,20 mm
    0,34 mm2 = 7 x 0,25 mm
    0,5 mm2 = 7 x 0,30 mm
    - Core insulation of PE, compound type 2YL1
    - Core colours to DIN 47100 with colour repetition
    - Core wrapping with foil
    - Tinned copper braided screening, coverage approx. 85 %
    - Special PVC outer sheath YM2 grey to DIN VDE 0207 part 5
    - Version Yv with reinforced outer sheath of special PVC YM2 black for underground
    laying
    - PVC outer sheath self-extinguishing and flame retardant according to IEC 60332-1
Technical Data  
Temperature range : Flexing -5ºC to + 70ºC
    Fixed installation -30ºC to + 80ºC
Conductor resistance : (loop) at 20ºC
    0,22 mm2 max. 186 Ohm/km
    0,34 mm2 max. 115 Ohm/km
    0,5 mm2 max. 78,5 Ohm/km
Operating voltage : (peak voltage)
    Max. 250 V (not for purposes of high current and power installation)
Test Voltage : Core/core 2000 V
    Core/screen 1000 V
Insulation resistance : Min. 5 GOhm x km
Mutual Capacitance : at 800 Hz
    > 4 pairs max. 60 nF/km
    < 4 pairs values extended by 20%
Impedence : 100 Ohm + 15
Minimum bending radius : Flexing : 12 x cable
    Fixed installation : 7,5 x cable
Application : The PE-insulated data cable is designed for computer application and data transmission.
    It is specially designed for wiring data systems with transmission rates up to 10MB/s, eg.
    for interfaces of types RS 422, RS 485. The twisted pair lay-up prevents electrical
    unbalances within the cable and this effectively suppresses cross-talk effect.
    These cables are designed for limited flexible use as well as for fixed installation in dry
    and damp interiors. Yv version reinforced with a black outer sheath suitable for outdoor
    and indoor use as well as for direct burial.
LI2YCY (Grey)

LI2YCY (Black for underground laying)