LiYY  
LiY-CY  
LiYY-Twisted Pair  
LiYCY-Twisted Pair  
Li2YCY-PiMF  
YSLYCY-JZ  
YSLYCY-JB  
LiYCY-OZ  
LiYCY-JZ  
Li2YCY  
LiY-CY
350 - 500 V
Technical Data  
Temperature range : Flexing -5ºC to + 80ºC
    Fixed installation -40ºC to + 80ºC
Nominal voltage : 0,14 mm2 = 350 V > 0,25 mm2 = 500 V
Test Voltage : Core/core 1200 : core/screen 800 V
Breakdown Voltage : min. 2400 V
Insulation resistance : min. 200 MOhm x km
Capacitance : (approx value) at 800 HZ
    core/core at 0,14mm2 = 120 pF/m
    core/core > 0,25mm2 = 150 pF/m
    core/screen at 0,14mm2 = 240 pF/m
    core/screen > 0,25mm2 = 270 pF/m
Inductance : approx 0,65 mH/km
Impedence : approx 78 Ohm
Coupling resistance : max. 250 Ohm/km
Minimum bending radius : Flexing : 10 x cable
    Fixed installation : 5 x cable
Radiation resistance : up to 80 x 1.000.000 cJ/kg (up to 80 Mrad)
Cable Construction : - Bare copper, fine wire conductors stranded to IEC 60228 cl 5
    - Special PVC core insulation T12
    - Colour coded to DIN 47100, but without colour repetition
    - Core wrapping with foil
    - Drain-wire, tinned
    - Tinned, copper braided screen, approx. 85% coverage
    - Special PVC outer sheath
    - Colour grey
    - Extensively oil resistant
    - PVC self-extinguishing and flame retardant according to IEC 60332-1
Application : This cable are used as junction or connecting cables in control, measuring and signaling
    technology as well as in data signalling technology as well as in data processing and office
    technology. Ideally suited for all types of connections on mobile equipment. The tight
    copper screening provides optimum protection against external electrical interference.